Terminal connections for input calibration
Calibration Stage Signal type Terminal
RTD Inputs
RTD Simulator A 2
RTD Simulator B 3
RTD Simulator Bsense 4
Input calibration procedure
When the
display shows
Action/Description
ENT
ï
Put the instrument in setup mode and scroll through the main menu
CIPn
Press Å or ì
CIPy
Calibrate inputs? Start No
Connect the current source to the inputs (for connections see over page).
-200
Set the RTD Simulator to -200 °C Calibrate Skip
700P
Set the RTD Simulator to 700 °C Calibrate Skip
-100
Set the RTD Simulator to -100 °C Calibrate Skip
200P
Set the RTD Simulator to 200 °C Calibrate Skip
AL=Y
Continue with the setup sequence.
Note 1: To discard changes to calibration and setup you can remove the power at this point.
Note 2: If the display shows OPEn check that the input simulator is properly connected.
Note 3: The values shown are for Pt100 inputs, see the table above for Ni120 inputs.
Terminal connections for output calibration
Calibration Stage Signal type Terminal
Analogue Current Output
mA output + 14
mA output − 15
Analogue Voltage Output
V output + 14
V output − 16