• Installation
General
These units must only be installed by qualified staff in accordance with
the information given in this manual and all relevant national electrical
wiring and safety rules must be followed.
Locate the instrument in an area that is free from dust, moisture and
corrosive gases.
Connections
Strip wires to 7 mm from the ends. Use a suitable ferrule for multi-
stranded wires (do not solder).
Use 12-28 AWG Cu Wire rated for temperatures above 70 °C Only,
tighten to 4.5 lb-In.
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Terminal Signal
1
Not used
Input signals
2
A
3
B
4
B
sense
5
Not used
6
Not used
7
Link to change the set-up Security Link
8
9 Neutral (−)
Power supply
10 Live (+)