• Installation
These units must only be installed by qualified staff in accordance with
the information given in this manual and all relevant national electrical
wiring and safety rules must be followed.
Locate the instrument in an area that is free from dust, moisture and
corrosive gases.
Connections
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Use 12-28 AWG Cu Wire rated for temperatures above 70 °C Only,
tighten to 4.5 lb-In. Strip wires to 7 mm from the ends. Use a suitable
ferrule for multi-stranded wires (do not solder).
Terminal Signal
1 12 V DC (out)
Input signal/sensor
2 Pull Up/Down
3 0V
4 Signal +
5 Signal
6 High voltage Signal +
Analogue outputs
Analogue
Output type
OP=I
OP=E
Current based output
Voltage based output
Toggle Accept
Analogue output
range
OPL=
4.00
Output low value
e.g., 4.00
-
Dec
-
Inc
-
Next
Accept
OPH=
20.00
Output high value
e.g., 20.00
-
Dec
-
Inc
Next
Accept
Output action
OP=d
OP=r
Direct
Reversed
Toggle Accept
Calibrate
Output?
COPn
COPy
Skip output calibration
Calibrate outputs
Toggle Accept
Setup Sequence (continued)