• Calibration
General
All instruments are fully calibrated before leaving the factory and
should not need adjustment until the next scheduled calibration.
Equipment requirements
• A suitable signal source (mA or V) for the inputs
• Two accurate digital multimeters (accurate to 0.05 mV and ±0.1 A)
• A suitable regulated power supply, e.g., RPS/240 V AC/24 V DC/x
• Flat bladed screwdriver (blade width less than 2.54 mm/0.1 inch)
Digital multimeters are frequently better at measuring voltages than
currents, so you may wish to measure the voltage across an accurate
standard resistor (say 10 Ω ±0.05 %) when monitoring current signals.
If you have a Mann Industries Portacal 1000 calibrator you will not
need the second multimeter or the regulated power supply.
Terminal connections for calibration
Model Number Cat. No. Channel Signal Signal type Terminal
TWI-1/4-20 mA 7940010159 One
4-20 mA input
DC milliamp source + 1
DC milliamp source − 3
4-20 mA output
mA output + 4
mA output − 6
TWI-1/0-10 V 7940011660 One
0-10 V input
DC Voltage source + 1
DC Voltage source − 3
4-20 mA output
mA output + 4
mA output − 6
Note: check all connection details against the instrument top label.