Weidmuller PT 100/4 signal conditioners for current output Uživatelský manuál Strana 12

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 18
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 11
30
Example
Chosen measuring range: -50 ... +150 °C
Set minimum temperature (-50 °C)
on the PT 100 simulator and calibrate the signal conditioner out-
put signal to 4.000 mA using the null potentiometer.
Mean temperatur e = (ϑ
max
+ ϑ
min
)/2
= (150 °C + (-50 °C))/2
= 50 °C
Set the 50 °C value on the PT 100 simulator
Then determine I: I = measured value from measuring
instrument - 12.000 mA
I = 11.940 mA - 12.000 mA
= -0.060 mA
Then calibrate the output signal to (12.000 mA - I) using the
span potentiometer i.e. her e an example.
"12.000 mA - (-0.060 mA) = 12.060 mA"
Then set the maximum temperature on the PT 100 simulator and
calibrate the output signal to 20.000 mA using the lin potentiome-
ter.
Zobrazit stránku 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 18

Komentáře k této Příručce

Žádné komentáře