Sensor diagnostics
You can order either upscale or downscale burnout protection and use
alarm channel one as a sensor burnout alarm if required.
The display shows:
OPEN when the input is open circuit
Ovr to indicate an over-range input
-Ovr to indicate an under-range input
R
eviewing the setup
For review mode, press the
Å and ì keys simultaneously.
Press the
Å and ì keys to move through the setup sequence (see
table). Greyed items in the setup table are not shown in review mode.
A 10 s timeout applies for review mode or you can press to quit.
Note: You can use review mode while the instrument is in service and
the analogue and alarm outputs will still operate correctly.
C
learing tripped alarms
You can acknowledge a tripped alarm by simply pressing the key for
that channel ( ï for Alarm 1 or ENT for Alarm 2).
D
isplaying the alarm setpoints
To check a setpoint, simply press the key for that channel ( ï for Alarm
1 or ENT for Alarm 2). If the alarms are disabled the display will show --
-- . If channel one is set-up as a burnout alarm it will show A1=0.
A
djusting the alarm setpoints
To change a setpoint, hold down the key for that channel ( ï for Alarm
1 or ENT for Alarm 2). You will then be able to change the value using
the arrows. Release the key to save the value.
Note: There are limits for the setpoint values that depend on the input
range setting and you cannot change the value if setpoint security is
on.