Protection according to IEC
61024-1, IEC 61312-1
Protection according to IEC
60364-4-443
Fig. 1 Overvoltage protective equipment in TN network
Fig. 2 Overvoltage protective equipment in TT Network with the 3+1 PU Module
1 Main supply system
2 Electrical circuit distributor
3 Branch circuit area
4 Main equipotential bonding strip
5 Overvoltage protection protective equipment Class I for lightning protection potential equalizer
5a 3+1 PU Unit with N-PE Lightning current arrestor
6 Main equipotential bonding conductor
7 Overvoltage protection-protective equipment Class II PU 3 C / PU 4 C
8 Overvoltage protection-protective equipment Class III PU D in the TN System
8a Overvoltage protection-protective equipment Class III PU D in the TT System
9 9a Overvoltage protection protective equipment Class II PU 3+1 C for TT System
10 RCD ( Residual-current device)
11 Arrester disconnector
HAK Service panel
R Earth
R
e
Equipment earth
Wh Measuring device
F1 Input terminal fuse
F2 Fuse for PUxB necessary only by max. 160 A (depending on type of routing ), if F1> 160 A.
F3 Fuses for Electrical circuit distributor
F4 Fuse for PUxC necessary only by max. 125 A (depending on type of routing), if F1> 125 A.
F5 Circuit breaker 16 A
*1) Construction before taking measurements should be agreed with the local ESC.