Weidmuller PT 100/3 sig conditioners for voltage output Uživatelský manuál Strana 12

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 12
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 11
18
3. Add 1% of the temperature span to the selected "minimum"
temperature and set this value on a PT 100 simulator (when
using a precision resistance decade, where necessary ob-
serve DIN IEC 751 conversion table from °C to !) and cali-
brate the signal conditioner output signal to 0.100 V using
the null potentiometer. (The potentiometers are located be-
hind the hinged cover).
4. Set the "maximum" selected temperature on a PT 100 simu-
lator (or precision resistance decade) and calibrate the signal
output to 10.000 V using the Span potentiometer.
5. Repeat steps 3 and 4 (approx. 2-3 times), until the required
accuracy is achieved.
4.3 Setting the DIP switches
Warning!! The signal conditioner PT 100 must be protected
against a direct electrostatic discharge when setting
the DIP switches.
Zobrazit stránku 11
1 2 ... 7 8 9 10 11 12

Komentáře k této Příručce

Žádné komentáře