26
8 Technical data
Input
Sensor types PT 100/2 Select C, PT 100/3 Select
C according to DIN IEC 751
Input current 1.35 mA ... 1.45 mA ... 1.60 mA
Conductor resistance ≤ 50 Ω (3-wire)
Input range -200 ... +800 °C adjustable using
DIP switches
Offset input range up to +25 % possible
Output
Current output adjustable using DIP switches
Load resistance ≤ 500 Ω
Accuracy ± 0.5 % from end value
Temperature coefficient
Measurement range
≥ 200 K ≤ 200 ppm/K (typ. 80 ppm/K)
≥ 100 K; < 200 K ≤ 250 ppm/K (typ. 100 ppm/K)
≥ 40 K; < 100 K ≤ 500 ppm/K (typ. 200 ppm/K)