13
The declarations of conformity are, in accordance with the above-
mentioned EU-Guideline, Article 10, held at the following address
for the relevant authorities:
Weidmüller Interface GmbH & Co.
Postfach 3030
D-32720 Detmold
7 Technical data
Input
Input signal 4 ... 20 mA
Input voltage, max. 7 V
Input current, max. 25 mA
Output
Output signal 0 ... 20 mA or 4 ... 20 mA
or 0 ... 10 V
Load resistance ≤ 500 Ω (0 ... 20 mA, 4 ... 20 mA)
≥ 1 kΩ (0 ... 10 V)
Accuracy by T
u
= 23 °C < 0.2 % from end value
Temperature coefficient ≤ 250 ppm/K from measured value
Step response time ≤ 30 ms (typ. 20 ms)
Cut-off frequency (-3 dB) ≥ 15 Hz (typ. 20 Hz)
Komentáře k této Příručce